Upgrading of Asian Alcohol Corporation 1.5 MVA power substation 4.160 KV main circuit protection for normal and continuous production
요약
The purpose of this study is to determine the needs and requirements for a best design for the upgrading of Asian Alcohol Corporation (AAC) 1.5 MVA power substation main circuit protection for a reliable and continuous production and cogeneration to other power source for total system flexibility. The research design adopted the descriptive analytical study that utilized document analysis and direct observation. The existing power system set-up was evaluated using the plant single line diagram, equipment name plate rating, kilowatt hour (KWHr) meter reading, substation base and line data from the utility company to determine the system future capacity requirement, system short circuit and co-generation capability. The best upgrade design of AAC 1.5 MVA power substation main circuit protection while on continuous production was determined using the System Fault Analysis in conformity with the standards of the Philippine Electrical Code (PEC) 2000. The AAC 1.5 MVA 4.160 KV main circuit protection shall be a 600 ampere tripping current capacity, 8 KAIC, 20 KA, 3.6/ 7.2 KV, 3-phase for a reliable and continuous production. The study covers the data from the daily performance report of the power generation department and the monthly power utility company billing from operation year 2003-2005.
기술
Abstract only
추천 인용
De La Cruz, V. H. V. (2007). Upgrading of Asian Alcohol Corporation 1.5 MVA power substation 4.160 KV main circuit protection for normal and continuous production (Unpublished Master's special paper). Central Philippine University, Jaro, Iloilo City.
유형
Special paper주제
학과
College of Engineering정도
Master of Engineering선반 위치
GSL Theses 620.0072 D371
물리적 설명
viii, 67 leaves
Collections
다음 라이센스 파일이이 항목과 연관되어 있습니다.
Related items
Showing items related by title, author, creator and subject.
-
A proposed intervention to improve the power quality and system efficiency of Calinog substation feeder 2
Roquios, Jose Redmond Eric S. (2007)Rationale Iloilo II Electric Cooperative, Inc. (ILECO II) is an electric distribution utility which supply electric power to the central part of the Province of Iloilo. With the passage of the RA 9136 otherwise known as ... -
The effect of rewiring the electrical power distribution system on the output voltages and maintenance at Central Philippine University
Idemne, Vitini Edhard O. (2007)This study aimed to assess the effects of rewiring the Electrical Power Distribution System on output voltages and maintenance of electrical devices at CPU campus. Specifically it determined and compared the output voltages ... -
Proposed quality maintenance system for diesel power plant (abstract paper)
Longno, Gilbert S. (2002)Rationale/introduction of the study Diesel Power Plants assume a vital role in the global as well as countries’ economy by providing quick response to power generation demand whenever and where ever they are needed. The ...