Show simple item record

dc.contributor.adviserLagos, Gelvie C.
dc.contributor.authorSilvederio, Julienne Marie B.
dc.contributor.authorSultan, Mycka Murielh S.
dc.contributor.authorTabiolo, Franz J.
dc.contributor.authorCabig, Denver C.
dc.date.accessioned2022-09-13T00:55:47Z
dc.date.available2022-09-13T00:55:47Z
dc.date.issued2020
dc.identifier.citationSilvederio, J. M. B. , Sultan, M. M. S. , Tabiolo, F. J. & Cabig, D. C. (2020). Study of the levels of harmonics in Central Philippine University (Unpublished thesis). Central Philippine University, Jaro, Iloilo City.en_US
dc.identifier.urihttps://hdl.handle.net/20.500.12852/2277
dc.descriptionAbstract onlyen_US
dc.description.abstractThis study was conducted to determine the levels of harmonics in Central Philippine University. Harmonic content and power factor data of the 12 transformer banks in the university were gathered using Fluke 1735-three phase power logger. Survey of the connected loads and defective electrical and electronic devices in all the buildings and functional areas of the university was conducted. The type of device were correlated with the harmonic order with the aid of Pearson Correlation Analysis. After the data analysis of the THDV and TDD content of each transformer bank, it was found out that the levels of harmonics in CPU electrical system are all in the acceptable range based on the IEEE Std-519. It has been found out that switched-mode power supply devices and ACU/Refrigerator have no linear relationship with the harmonic orders 3rd, 5th, and 7th. Variable Speed drives have moderate negative linear relationship with 7th harmonic content in line C. Lighting devices have moderate positive linear relationship with 7th harmonic content in line B. Heating devices have moderate negative linear relationship with 3rd harmonic content in line B and strong negative linear relationship with 7th harmonic content in line B. The levels of harmonics were not considered as the main contributors of the recorded defective devices. With the gathered and analyzed data, it has been concluded that the buildings in Central Philippine University are not susceptible to the impacts of harmonics. The gathered power factor and TDD per line in each bank have shown no significant linear relationship.en_US
dc.format.extentix, 509 leavesen_US
dc.language.isoenen_US
dc.subject.ddcFilipiniana Theses 621.3072 Si39en_US
dc.subject.lcshHarmonics (Electric waves)en_US
dc.subject.lcshCentral Philippine Universityen_US
dc.titleStudy of the levels of harmonics in Central Philippine Universityen_US
dc.typeSpecial paperen_US
dcterms.accessRightsNot publicly accessibleen_US
dc.description.bibliographicalreferencesIncludes bibliographical referencesen_US
dc.contributor.chairMolina, Dany C.
dc.contributor.committeememberJava, Alberto A.
dc.contributor.committeememberAcanto, Caesar Rico S.
dc.contributor.committeememberIdemne, Vitini Edhard O.
dc.contributor.departmentDepartment of Electrical Engineeringen_US
dc.description.degreeBachelor of Science in Electrical Engineeringen_US